Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Frame
286T
Full Load Efficiency
94.1 %
Motor Application
General Purpose
Drive End Bearing
6311
Voltage Rating
460, 230
Rotation
R
Epact Nominal Full Load Efficiency
92.4 %
Full Load Amps
35
Voltage
230/460
Frame Material
Steel
Useable at 208V
Yes
Mounting
Rigid Base
Frame Size
Shaft Input, Not a C-Face
RefPicture
EMDP
Brake Feature
No
BALD Family Names
Premium Efficient, Nema Premium™
Mult. Sym.
L1
Design
B
C Dimension
25.06 in
Motor Shaft Size
1 7/8 in
Open End Bearing
6309
VoltCode
E1
Enclosure Designation
OPSB - Open Slotted Band
Product Line
RG
Full Load rpm
1770 rpm
Full Load Pf
85
Poles
4
Substitute Motor
M2535T
Motor Shaft Length
4 5/8 in
Washdown Duty
No
Efficiency Group
Premium Efficient
Phase
Three Phase
Service Factor
1.15
RPM
1800 rpm
Mounting Style
F-1
Enclosure
OPSB
Hz
60 Hz
Type
4052M
C Face Kit
40-1400
Weight
372.0 LB
EAN or UPC
781568105054
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back