Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Service Factor
1
Substitute Motor
M7062T
Washdown Duty
No
Efficiency Group
Premium Efficient
Motor Application
Explosion Proof
Hz
60 Hz, 50 Hz
Type
X1260M
Rotation
R
Mounting Style
F-1
C Dimension
32.12 in
Full Load Efficiency
94.5 %
Full Load rpm
1475 rpm, 1775 rpm
Poles
4
VoltCode
U
Mounting
Rigid Base
Brake Feature
No
Open End Bearing
6311
Mult. Sym.
L1
Motor Shaft Size
2 1/8 in
Useable at 208V
No
Motor Shaft Length
5 1/4 in
Enclosure Designation
XPFC - Explosion Proof Fan Cooled
Frame Material
Cast Iron
Design
B
Phase
Three Phase
Frame
324T
Drive End Bearing
6312
Voltage
190/380/230/460
RPM
1800 rpm, 1500 rpm
Full Load Pf
86
Frame Size
Shaft Input, Not a C-Face
RefPicture
EM7064T
BALD Family Names
Premium Efficient, Explosion Proof
Product Line
RG
Voltage Rating
190, 460, 230, 380
Enclosure
XPFC
Full Load Amps
46
Weight
767.0 LB
EAN or UPC
781568139264
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back