Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Motor Shaft Size
1 5/8 in
Hz
60 Hz, 50 Hz
Frame Size
Shaft Input, Not a C-Face
Voltage Rating
190, 460, 230, 380
VoltCode
U
Efficiency Group
Premium Efficient
Poles
4
Service Factor
1
RPM
1800 rpm, 1500 rpm
Useable at 208V
No
Product Line
RG
Drive End Bearing
6309
Full Load Amps
24
Full Load Pf
84
C Dimension
25 1/2 in
Washdown Duty
No
Enclosure
XPFC
Mounting
Rigid Base
Mounting Style
F-1
BALD Family Names
Premium Efficient, Explosion Proof
Motor Shaft Length
4 in
Frame Material
Cast Iron
Motor Application
Explosion Proof
Type
X0952M
Mult. Sym.
L1
Rotation
R
Full Load rpm
1465 rpm, 1765 rpm
Frame
256T
Enclosure Designation
XPFC - Explosion Proof Fan Cooled
Brake Feature
No
Substitute Motor
M7056T
RefPicture
EM7064T
Design
B
Voltage
190/380/230/460
Phase
Three Phase
Full Load Efficiency
93 %
Open End Bearing
6208
Weight
393.0 LB
EAN or UPC
781568139233
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back