Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Mult. Sym.
L1
Substitute Motor
M2536T
Type
4268M
Brake Feature
No
Useable at 208V
Yes
C Face Kit
42-1300
BALD Family Names
Premium Efficient, Nema Premium™
Motor Shaft Size
2 1/8 in
Efficiency Group
Premium Efficient
Hz
60 Hz
Phase
Three Phase
Full Load rpm
1180 rpm
Voltage Rating
460, 230
VoltCode
E1
Product Line
RG
RefPicture
EMDP
Enclosure Designation
OPSB - Open Slotted Band
Motor Application
General Purpose
Epact Nominal Full Load Efficiency
92.4 %
Design
B
Frame
326T
Rotation
R
RPM
1200 rpm
Motor Shaft Length
5 1/4 in
Open End Bearing
6311
Frame Material
Steel
Enclosure
OPSB
C Dimension
27.69 in
Drive End Bearing
6312
Full Load Amps
37
Full Load Pf
81
Mounting Style
F-1
Mounting
Rigid Base
Voltage
230/460
Service Factor
1.15
Poles
6
Washdown Duty
No
Full Load Efficiency
93.6 %
Frame Size
Shaft Input, Not a C-Face
Weight
463.0 LB
EAN or UPC
781568105085
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back