Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Washdown Duty
No
Epact Nominal Full Load Efficiency
91.7 %
Frame Material
Steel
Rotation
R
Phase
Three Phase
Voltage
230/460
Type
4252M
Motor Application
General Purpose
Efficiency Group
Premium Efficient
Full Load Efficiency
93.6 %
Open End Bearing
6311
Mounting Style
F-1
VoltCode
E1
Drive End Bearing
6312
C Face Kit
42-1300
Frame Size
Shaft Input, Not a C-Face
Service Factor
1.15
RefPicture
EMDP
BALD Family Names
Premium Efficient, Nema Premium™
Useable at 208V
Yes
Substitute Motor
M2532T
Product Line
RG
Poles
6
Full Load Pf
80
Mult. Sym.
L1
Mounting
Rigid Base
Full Load rpm
1180 rpm
Motor Shaft Size
2 1/8 in
Enclosure Designation
OPSB - Open Slotted Band
C Dimension
27.69 in
Full Load Amps
31
RPM
1200 rpm
Motor Shaft Length
5 1/4 in
Brake Feature
No
Voltage Rating
460, 230
Hz
60 Hz
Enclosure
OPSB
Frame
324T
Design
B
Weight
478.0 LB
EAN or UPC
781568105016
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back