Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Useable at 208V
No
Brake Feature
No
Rotation
R
Drive End Bearing
6311
Mounting
Rigid Base
Mounting Style
F-1
C Face Kit
40-1400
Frame Size
Shaft Input, Not a C-Face
Frame
284T
Motor Application
General Purpose
Enclosure Designation
OPSB - Open Slotted Band
RefPicture
EMDP
BALD Family Names
Premium Efficient, Nema Premium™
Voltage
230/460
Full Load Amps
19.5
Phase
Three Phase
Full Load Efficiency
92.4 %
Motor Shaft Length
4 5/8 in
VoltCode
F
Product Line
RG
Enclosure
OPSB
Epact Nominal Full Load Efficiency
90.2 %
Open End Bearing
6309
Washdown Duty
No
Poles
6
Mult. Sym.
L1
Hz
60 Hz
Type
4050M
Substitute Motor
M2524T
Voltage Rating
460, 230
Service Factor
1.15
Motor Shaft Size
1 7/8 in
Full Load rpm
1180 rpm
Full Load Pf
78
Efficiency Group
Premium Efficient
RPM
1200 rpm
Design
B
Frame Material
Steel
Weight
375.0 LB
EAN or UPC
781568104873
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back