Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Open End Bearing
6309
Motor Application
Severe Duty
Useable at 208V
No
Design
B
Frame
284T
Efficiency Group
Standard Efficient
C Face Kit
10-1305
Product Line
RG
HP [Min]
25
Full Load rpm
1770 rpm
Voltage
460
VoltCode
G
Frame Size
284T
Motor Shaft Size
1 7/8 in
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Hz
60 Hz
Full Load Efficiency
93.6 %
RPM
1800 rpm
Drive End Bearing
6311
Phase
Three Phase
Motor Shaft Length
4 5/8 in
Poles
4
Brake Feature
No
Type
1046M
Service Factor
1.15
Frame Material
Cast Iron
Epact Nominal Full Load Efficiency
92.4 %
Model
841 XL
Mult. Sym.
L1
C Dimension
27.56 in
Voltage Rating
460
Full Load Pf
84
Rotation
R
Enclosure
Totally Enclosed
Full Load Amps
30
Mounting
Foot Mounted
Mounting Style
F-1
RefPicture
ECP03
Washdown Duty
No
Weight
441.0 LB
EAN or UPC
781568196625
NEMA Premium