Baldor-Reliance® severe duty motors include features designed to protect against contamination, moisture, vibration and corrosion. These motors use Super-E® premium efficient electrical designs which are built to handle demanding duty cycles, provide high starting and peak torques, and operate over wide speed ranges. Severe Duty motors provide safe, long operating life, reliable performance, and reduced energy consumption in the toughest applications.
applications
Petro-chemical plants
Mines
Foundries
Pulp and Paper plants
Waste management facilities
Chemical plants
Tropical climates
features
Heavy duty cast iron construction
Premium efficient electrical designs
Enhanced ingress protection
Corrosion resistant epoxy finish
caution
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Useable at 208V
No
Phase
Three Phase
Motor Shaft Length
2 1/4 in
Poles
4
Design
B
Mounting
Foot Mounted
Full Load Pf
82
Type
0532M
Full Load Efficiency
86.5 %
Hz
60 Hz
Mounting Style
F-1
Model
XEX
Mult. Sym.
L1
Washdown Duty
No
Voltage Rating
460
C Dimension
12 3/4 in
Product Line
RG
RefPicture
ECP03
Motor Shaft Size
7/8 in
VoltCode
G
Voltage
460
Enclosure
Totally Enclosed
Full Load Amps
2.7
BALD Family Names
Premium Efficient, Nema Premiumâ„¢, Severe Duty
Rotation
R
Epact Nominal Full Load Efficiency
84 %
Brake Feature
No
Service Factor
1.15
HP [Min]
2
C Face Kit
35-1300
Full Load rpm
1725 rpm
Drive End Bearing
6205
Motor Application
Severe Duty
Open End Bearing
6203
Frame Size
Shaft Input, Not a C-Face
Efficiency Group
Standard Efficient
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Frame Material
Cast Iron
RPM
1800 rpm
Frame
145T
Weight
73.0 LB
EAN or UPC
781568136546
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back