Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Useable at 208V
No
Open End Bearing
6311
Phase
Three Phase
Enclosure Designation
XPFC - Explosion Proof Fan Cooled
Washdown Duty
No
Frame
324T
Design
B
Efficiency Group
Premium Efficient
Voltage Rating
190, 460, 230, 380
Full Load Pf
86
Enclosure
XPFC
Motor Application
Explosion Proof
Motor Shaft Size
2 1/8 in
Rotation
R
VoltCode
U
Drive End Bearing
6312
Full Load Amps
46
Full Load rpm
1475 rpm, 1775 rpm
Type
X1260M
Motor Shaft Length
5 1/4 in
Mounting
Rigid Base
Brake Feature
No
Hz
60 Hz, 50 Hz
Poles
4
Product Line
RG
RPM
1800 rpm, 1500 rpm
Mounting Style
F-1
Service Factor
1
RefPicture
XPCI
Mult. Sym.
L1
Voltage
190/380/230/460
C Dimension
32.12 in
Frame Size
Shaft Input, Not a C-Face
Full Load Efficiency
94.5 %
BALD Family Names
Premium Efficient, Explosion Proof
Weight
834.0 LB
EAN or UPC
781568296011
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back