Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
RPM
1200 rpm
RefPicture
EMTECI
Mounting Style
F-1
Phase
Three Phase
Design
A
Epact Nominal Full Load Efficiency
91.7 %
Motor Shaft Length
5 1/4 in
C Dimension
30.28 in
Full Load rpm
1180 rpm
Motor Shaft Size
2 1/8 in
Poles
6
Voltage
230/460
BALD Family Names
Premium Efficient, Nema Premium™
VoltCode
F
Service Factor
1.15
Washdown Duty
No
Drive End Bearing
6312
C Face Kit
12-1105
Frame Material
Cast Iron
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Efficiency Group
Premium Efficient
Full Load Pf
79
Frame
324T
Hz
60 Hz
Type
1080M
Full Load Amps
32
Useable at 208V
No
Voltage Rating
460, 230
Mounting
Rigid Base
Frame Size
Shaft Input, Not a C-Face
Rotation
R
Brake Feature
No
Mult. Sym.
L1
Open End Bearing
6309
Enclosure
TEFC
Motor Application
General Purpose
Product Line
RG
Substitute Motor
M4111T
Full Load Efficiency
93 %
Weight
504.0 LB
EAN or UPC
781568103258
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back