Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
VoltCode
E1
Enclosure Designation
OPSB - Open Slotted Band
Drive End Bearing
6309
Substitute Motor
M2511T
Motor Shaft Length
4 in
Hz
60 Hz
Motor Shaft Size
1 5/8 in
Open End Bearing
6208
Full Load Efficiency
91.7 %
Full Load rpm
1180 rpm
Full Load Pf
71
Frame Size
Shaft Input, Not a C-Face
RefPicture
EMDP
Voltage
230/460
Poles
6
Service Factor
1.15
Voltage Rating
460, 230
Product Line
RG
Motor Application
General Purpose
RPM
1200 rpm
Mounting Style
F-1
Type
3954M
Design
B
C Dimension
23.19 in
Full Load Amps
14.3
BALD Family Names
Premium Efficient, Nema Premium™
Washdown Duty
No
Useable at 208V
Yes
Mult. Sym.
L1
Epact Nominal Full Load Efficiency
90.2 %
Phase
Three Phase
Brake Feature
No
C Face Kit
39-1400
Frame
256T
Efficiency Group
Standard Efficient
Rotation
R
Enclosure
OPSB
Frame Material
Steel
Mounting
Rigid Base
Weight
245.0 LB
EAN or UPC
781568104804
NEMA Premium
My Applied Catalog