Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
C Dimension
44.24 in
Model
841 XL
Full Load Pf
85
Frame Size
445T
Voltage
460
Brake Feature
No
Full Load Amps
173
Service Factor
1.15
Useable at 208V
No
Open End Bearing
6314
Washdown Duty
No
Mounting Style
F-1
Frame Material
Cast Iron
Full Load Efficiency
95.8 %
Epact Nominal Full Load Efficiency
95 %
Phase
Three Phase
Motor Shaft Size
3 3/8 in
Frame
445T
RPM
1800 rpm
VoltCode
G
Full Load rpm
1785 rpm
Design
B
C Face Kit
18-1302
Hz
60 Hz
Efficiency Group
Standard Efficient
HP [Min]
150
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Enclosure
Totally Enclosed
Rotation
R
Mult. Sym.
D3
Motor Application
Severe Duty
Motor Shaft Length
8 1/2 in
Type
1888M
Mounting
Foot Mounted
Poles
4
Product Line
RG
Drive End Bearing
6319
Voltage Rating
460
RefPicture
CRUSH
Weight
1914.0 LB
EAN or UPC
781568196700
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back